Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2020, 05:21 PM
  • 22 0752_22 0751_12112020_104100.mp4

Date
12/11/2020
W/O
0860113
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00821
PipeID
P17109
Time
9:21 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1667
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
LA VERNE
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Capital Improvement Program Assesment
Project
20201211SHO_PUDDINGSTONE_TRUNK_SECTION_1_2
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0752
Downstream MH
22 0751
Dir. of Survey
Downstream
Length Surveyed
348.3 ft.
Total Length
348.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 22 0752 to 22 0751
MH: 22 0752MH: 22 0751downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 7523.8 ft. MGO - General Observation - MAG COAT THROUGHOUT3.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"49.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"201 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"253 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"301.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"344.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"346.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348.3 ft. AMH - Downstream Manhole, Survey Ends - MH 751

Observations (14)

DistanceCodeObservation
0MWM
0MWL
148.9TFC
301.4TFC
0AMHMH 752
5.5TBA
344.5TFA
49.5TFC
253TFC
348.3AMHMH 751
3.8MGOMAG COAT THROUGHOUT
3.8SAV
201TFC
346.4SAV

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-12-11T09:21:05-08:00
documentation
OBREGON, RAMIREZ, BRAR
is_lateral_inspection
false