Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2019, 07:13 PM
  • 08-0367-08-0366.mpg

Date
06/24/2019
W/O
200347
Weather
Dry
Operator/Surveyor
Oscar Villareal
Sewer ID
Z00003
PipeID
P00419
Time
12:13 PM
Certificate
U-1113-06019665
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Jetting
Media Label
03
Sewer Name
08 Davidson City Trunk
City
City of Carson, CA
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
12
Purpose
Pre-Rehabilitation Survey
Project
Davidson_City_TS_Rehab
Sewer Type
Gravity
Material
NRCP
Lining Method
Cured in Place
Shape
Circular
Height
18 in.
Upstream MH
08 0367
Downstream MH
08 0366
Dir. of Survey
Downstream
Length Surveyed
141.6 ft.
Total Length
142 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 08 0367 to 08 0366
MH: 08 0367MH: 08 0366downstream0 ft. AMH - Upstream Manhole, Survey Begins - MH 3670 ft. MWLS - Water Level, Sag in pipe, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 3670 ft. MWL - Water Level, 5 % of cross sectional area0 ft.46 ft. TFA - Tap Factory Made Active, at 12 o'clock, 6", within 8 inches of joint: YES77 ft. TFA - Tap Factory Made Active, at 12 o'clock, 6", within 8 inches of joint: YES77.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, 6", within 8 inches of joint: YES102 ft. TFC - Tap Factory Made Capped, at 12 o'clock, 6", within 8 inches of joint: YES126 ft. TFA - Tap Factory Made Active, at 12 o'clock, 6", within 8 inches of joint: YES127.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, 6", within 8 inches of joint: YES141.6 ft. AMH - Downstream Manhole, Survey Ends - MH 366142 ft. AMH - Downstream Manhole, Survey Ends - MH 366

Observations (13)

DistanceCodeObservation
141.6AMHMH 366
0AMHMH 367
102TFC
77TFA
46TFA
126TFA
0MWLS
0AMHMH 367
77.4TFA
0MWL
142AMHMH 366
127.8TFA
0

Properties (3)

customer
LACSD
datetime
2019-06-24T12:13:01-07:00
is_lateral_inspection
false