Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2018, 08:09 PM
  • Section#6_30 0047_30 0046__6112018__I0023.mp4

Date
06/11/2018
W/O
0706884
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00878
PipeID
P17750
Time
1:09 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0023
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
HERMOSA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20180608DF_SOUTH_BAY_CITIES_MAIN_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
30 0047
Downstream MH
30 0046
Dir. of Survey
Downstream
Length Surveyed
193.6 ft.
Total Length
193.6 ft.
Structural Index
3
Structural Quick
3F2F
Structural Rating
185
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
185
Pipe schematic from manhole 30 0047 to 30 0046
MH: 30 0047MH: 30 0046downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:10 PM0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 80% MAG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start51.5 ft. MGP - General Photograph111 ft. MGP - General Photograph188.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish188.5 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 80% MAG188.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish193.6 ft. AMH - Downstream Manhole, Survey Ends - 1:27 PM

Observation photos (4)

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 80% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 80% MAG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    51.5 ft. - General Photograph

  • General Photograph

    111 ft. - General Photograph

Observations (12)

DistanceCodeObservation
0MWL
51.5MGP
2SAP
188.6SAP
0AMH1:10 PM
111MGP
188.4SSS
2SZ80% MAG
193.6AMH1:27 PM
2SSS
0MWM
188.5SZ80% MAG

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2018-06-11T13:09:11-07:00
documentation
FRANKLIN, PARAISO, IGNACIO
is_lateral_inspection
false