Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2018, 03:54 PM
  • Section#4_30 0056_30 0055__6112018__I0023.mp4

Date
06/11/2018
W/O
0706884
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00878
PipeID
P17759
Time
8:54 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0023
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
HERMOSA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20180608DF_SOUTH_BAY_CITIES_MAIN_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
30 0056
Downstream MH
30 0055
Dir. of Survey
Downstream
Length Surveyed
151 ft.
Total Length
151 ft.
Structural Index
3
Structural Quick
5E3E
Structural Rating
313
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
321
Pipe schematic from manhole 30 0056 to 30 0055
MH: 30 0056MH: 30 0055downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:56 AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGP - General Photograph - U/S ZOOMED2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 50% MAG2 ft. MGP - General Photograph - U/S ZOOMED52 ft. MGP - General Photograph128.1 ft. RTJ - Roots Tap Joint, from 11 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Start128.1 ft. MGP - General Photograph128.1 ft. MGP - General Photograph128.1 ft. MGP - General Photograph128.1 ft. SRV - Surface Reinforcement Visible, from 11 to 04 o'clock, within 8 inches of joint: YES128.1 ft. MGP - General Photograph - SEAM/JOINT TAPE132.6 ft. MGP - General Photograph132.7 ft. MGP - General Photograph139 ft. MGP - General Photograph143.9 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES150.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish150.4 ft. SRP - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES150.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish150.4 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 50% MAG150.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish150.4 ft. RTJ - Roots Tap Joint, from 11 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Finish151 ft. AMH - Downstream Manhole, Survey Ends - 9:20 AM

Observation photos (15)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 50% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 50% MAG

  • General Photograph

    52 ft. - General Photograph

  • Roots Tap Joint, from 11 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Start

    128.1 ft. - Roots Tap Joint, from 11 to 04 o'clock, 15 %, within 8 inches of joint: YESR, Start

  • General Photograph

    128.1 ft. - General Photograph

  • General Photograph

    128.1 ft. - General Photograph

  • General Photograph

    128.1 ft. - General Photograph

  • Surface Reinforcement Visible, from 11 to 04 o'clock, within 8 inches of joint: YES

    128.1 ft. - Surface Reinforcement Visible, from 11 to 04 o'clock, within 8 inches of joint: YES

  • General Photograph - SEAM/JOINT TAPE

    128.1 ft. - General Photograph - SEAM/JOINT TAPE

  • General Photograph

    132.6 ft. - General Photograph

  • General Photograph

    132.7 ft. - General Photograph

  • General Photograph

    139 ft. - General Photograph

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES

    143.9 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
150.3SRV
0MWL
2SSS
128.1RTJ
128.1MGP
150.4SRP
132.7MGP
139MGP
150.4SSS
128.1MGP
2SRV
132.6MGP
2SAP
151AMH9:20 AM
128.1MGP
2MGPU/S ZOOMED
0MWM
150.4SZ50% MAG
0AMH8:56 AM
2SZ50% MAG
52MGP
150.4SAP
150.4RTJ
2MGPU/S ZOOMED
128.1SRV
143.9SRC
128.1MGPSEAM/JOINT TAPE

Properties (6)

custom_field_three
AGGREGATE PROJECTING AND TAP ROOTS
custom_field_two
2
customer
LACSD
datetime
2018-06-11T08:54:56-07:00
documentation
FRANKLIN, PARAISO, IGNACIO
is_lateral_inspection
false