- Date
- 09/20/2017
- W/O
- 0646302
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z01180
- PipeID
- P01467
- Time
- 3:06 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6826
- Sewer Name
- G JOINT OUTFALL G - UNIT 8
- City
- COMPTON
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 17
- Purpose
- Capital Improvement Program Assesment
- Project
- 20170916MDM_JOINT_OUTFALL_G_UNIT_8
- Material
- RCP-CTL
- Shape
- Circular
- Height
- 36 in.
- Upstream MH
- G 0144
- Downstream MH
- G 0143
- Dir. of Survey
- Downstream
- Length Surveyed
- 407.6 ft.
- Total Length
- 407.6 ft.
- Structural Index
- 3
- Structural Quick
- 3O00
- Structural Rating
- 243
- O&M Index
- 4
- O&M Quick
- 5232
- O&M Rating
- 16
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 259
Pipe schematic from manhole G 0144 to G 0143 Observation photos (7)

2 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

5.4 ft. - General Observation - TILES 20% MISSING & PARTIAL START 10:00 TO 2:00

8.9 ft. - General Observation - MAG COAT WITH GREASE 30% START

11.3 ft. - General Observation - MISSING TILES 30%

68.1 ft. - General Observation - 30% MISSING TILES START 10:00 TO 2:00

149.2 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start

336.1 ft. - General Observation - MISSING & PARTIAL TILES 60% START 10:00 TO 2:00