Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 14, 2017, 05:42 PM
  • Section#1_C 0351_C 0350__12142017__G6882.mp4

Date
12/14/2017
W/O
0643523
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00139
PipeID
P09814
Time
9:42 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6882
Sewer Name
C JOINT OUTFALL C - UNIT 8A
City
LONG BEAH
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
09
Purpose
Routine Assessment
Project
20171214DF_JOINT_OUTFALL_C_UNIT_8A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
C 0351
Downstream MH
C 0350
Dir. of Survey
Downstream
Length Surveyed
213.7 ft.
Total Length
213.7 ft.
Structural Index
3
Structural Quick
5H3Q
Structural Rating
572
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
572
Pipe schematic from manhole C 0351 to C 0350
MH: C 0351MH: C 0350downstream0 ft. AMH - Upstream Manhole, Survey Begins - 9:53 AM0.1 ft. MWM - Water Mark, 30 %of cross sectional area0.1 ft. MWL - Water Level, 25 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start165.3 ft. MGP - General Photograph213.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish213.7 ft. MSA - Survey Abandoned - NOT ENOUGH FLOW213.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish213.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish213.7 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    165.3 ft. - General Photograph

Observations (13)

DistanceCodeObservation
2SRV
213.7SSS
2SSS
2SAV
0.1MWM
213.7MSANOT ENOUGH FLOW
213.7SAV
0AMH9:53 AM
2SAP
213.7SAP
0.1MWL
213.7SRV
165.3MGP

Properties (5)

custom_field_two
5
customer
LACSD
datetime
2017-12-14T09:42:37-08:00
documentation
FRANKLIN, BRAR, VENDRYES, PARAISO
is_lateral_inspection
false