Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 24, 2020, 07:08 AM
  • 22 0117_22 0116_11232020_232056.mp4

Date
11/23/2020
W/O
854905
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00805
PipeID
P16359
Time
11:08 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8256
Sewer Name
DISTRICT #22 MAIN TRUNK
City
COVINA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
26
Purpose
Routine Assessment
Project
WO_854905_TV22151_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
22 0117
Downstream MH
22 0116
Dir. of Survey
Downstream
Length Surveyed
296.2 ft.
Total Length
296.2 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
275
O&M Index
2
O&M Quick
412K
O&M Rating
120
Overall Index
2
Overall Quick
Overall Rating
395
Pipe schematic from manhole 22 0117 to 22 0116
MH: 22 0117MH: 22 0116downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 22 01170 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 40% MAG COAT18.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start18.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start29 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"37.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"93.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"215.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"293.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish293.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish293.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish296.2 ft. AMH - Downstream Manhole, Survey Ends - 22 0116296.2 ft. MGO - General Observation - COCKROACHES @ MANHOLE296.2 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (4)

  • General Observation - ROACHES @ MANHOLE

    0 ft. - General Observation - ROACHES @ MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    18.2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES @ MANHOLE

    296.2 ft. - General Observation - COCKROACHES @ MANHOLE

Observations (22)

DistanceCodeObservation
0MWL
37.2TFC
0MGOROACHES @ MANHOLE
0AMH22 0117
18.2SSS
18.2SAP
150.9TFC
293.5SSS
215.7TFC
296.2AMH22 0116
208.1TFC
293.5DAGS
293.5SAP
296.2MGOCOCKROACHES @ MANHOLE
2DAGS
86.1TFA
2MGO40% MAG COAT
296.2MGOCONN @ MH 9 O'CLOCK/ACTIVE
199.5TFA
0MWM
93.9TFC
29TFA

Properties (7)

additional_info
630069112320201
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2020-11-23T23:08:38-08:00
documentation
PRO PIPE
is_lateral_inspection
false