Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 20, 2020, 08:05 AM
  • 18 0247_18 0246 _11202020_003130.mp4

Date
11/20/2020
W/O
855022
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00674
PipeID
P14075
Time
12:05 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8219
Sewer Name
EAST IMPERIAL HIGHWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
27
Purpose
Routine Assessment
Project
WO_855022_TV18005_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0246
Downstream MH
18 0247
Dir. of Survey
Upstream
Length Surveyed
327.3 ft.
Total Length
327.3 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
192
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
192
Pipe schematic from manhole 18 0246 to 18 0247
MH: 18 0246MH: 18 0247upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 02470.1 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish5.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish7.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"33.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"138.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"255.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"305.7 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start324.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start327.3 ft. AMH - Downstream Manhole, Survey Begins - 18 0246327.3 ft. MWM - Water Mark, 10 %of cross sectional area327.3 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (1)

  • Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.6 ft. - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
188.9TF
0AMH18 0246
71.7TF
0MWM
0MWL
327.3AMH18 0247
327.2IS
3CM
322CM
293.9TF
320.2TF
21.6IS

Properties (6)

custom_field_three
CRACKS THROUGHOUT
custom_field_two
3
customer
1
datetime
2020-11-20T00:05:38-08:00
documentation
PRO PIPE
is_lateral_inspection
false