Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 20, 2020, 07:49 AM
  • 18 0246_18 0245 _11202020_000448.mp4

Date
11/19/2020
W/O
855022
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00674
PipeID
P14074
Time
11:49 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8219
Sewer Name
EAST IMPERIAL HIGHWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_855022_TV18005_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0245
Downstream MH
18 0246
Dir. of Survey
Upstream
Length Surveyed
295.4 ft.
Total Length
295.4 ft.
Structural Index
3
Structural Quick
4D3E
Structural Rating
194
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
194
Pipe schematic from manhole 18 0245 to 18 0246
MH: 18 0245MH: 18 0246upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 02460.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish47.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"165.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish165.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start165.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"273.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start287.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"288.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES288.2 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES295.4 ft. MWM - Water Mark, 10 %of cross sectional area295.4 ft. MWL - Water Level, 5 %of cross sectional area295.4 ft. AMH - Downstream Manhole, Survey Begins - 18 0245

Observation photos (4)

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    7.2 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    7.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    130 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
7.3CL
0MWM
295.4AMH18 0246
247.5TFA
0MWL
7.2CM
129.9TFA
8TF
130CM
130FM
21.5CM
0AMH18 0245
294.8FM

Properties (6)

custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-11-19T23:49:41-08:00
documentation
PRO PIPE
is_lateral_inspection
false