Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 20, 2020, 08:46 AM
  • 18 0245_18 0244 _11202020_010003.mp4

Date
11/20/2020
W/O
855022
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00674
PipeID
P14073
Time
12:46 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8219
Sewer Name
EAST IMPERIAL HIGHWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_855022_TV18005_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0245
Downstream MH
18 0244
Dir. of Survey
Downstream
Length Surveyed
295 ft.
Total Length
295 ft.
Structural Index
3
Structural Quick
4B3G
Structural Rating
188
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
188
Pipe schematic from manhole 18 0245 to 18 0244
MH: 18 0245MH: 18 0244downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02450 ft. MWL - Water Level, 5 %of cross sectional area9.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start50 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish50.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start109.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"293.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish295 ft. AMH - Downstream Manhole, Survey Ends - 18 0244

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    50.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
295AMH18 0244
0MWM
293.3FM
0AMH18 0245
109.6TF
50.3FM
9.2CM
0MWL
50CM

Properties (6)

custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-11-20T00:46:27-08:00
documentation
PRO PIPE
is_lateral_inspection
false