Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2020, 08:08 AM
  • 18 0239_18 0238 _12012020_001406.mp4

Date
12/01/2020
W/O
855022
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00674
PipeID
P14067
Time
12:08 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8225
Sewer Name
EAST IMPERIAL HIGHWAY TRUNK
City
LA MIRADA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_855022_TV18005_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0238
Downstream MH
18 0239
Dir. of Survey
Upstream
Length Surveyed
71.4 ft.
Total Length
71.4 ft.
Structural Index
4
Structural Quick
4A00
Structural Rating
48
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
48
Pipe schematic from manhole 18 0238 to 18 0239
MH: 18 0238MH: 18 0239upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 02390.4 ft. MGO - General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK0.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish60.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start71.4 ft. MWL - Water Level, 15 %of cross sectional area71.4 ft. AMH - Downstream Manhole, Survey Begins - 18 023871.4 ft. MWM - Water Mark, 25 %of cross sectional area71.4 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
11.3FM
0MWL
71.4AMH18 0239
71MGOCONNECTION AT MH, 3 AND 9 O'CLOCK
0AMH18 0238
0MWM
0MGOCONNECTION AT MH, 9 O'CLOCK
71FM

Properties (7)

additional_info
63007511240203
custom_field_three
CRACKS, FRACTURES
custom_field_two
3
customer
1
datetime
2020-12-01T00:08:15-08:00
documentation
PRO PIPE
is_lateral_inspection
false