Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2020, 06:25 AM
  • 22 1040_22 1039 _12022020_225403.mp4

Date
12/02/2020
W/O
854909
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00811
PipeID
P17409
Time
10:25 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8321
Sewer Name
IRWINDALE TRUNK, SECTION 1
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
WO_854909_TV22108_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
22 1040
Downstream MH
22 1039
Dir. of Survey
Downstream
Length Surveyed
625.7 ft.
Total Length
625.7 ft.
Structural Index
3
Structural Quick
3X00
Structural Rating
375
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
375
Pipe schematic from manhole 22 1040 to 22 1039
MH: 22 1040MH: 22 1039downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 10400 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2.5 ft. MGO - General Observation - MAG COAT2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"80.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"182.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"229.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"275.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"323.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"376.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"423.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"475 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"518.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"571.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"625.7 ft. AMH - Downstream Manhole, Survey Ends - 22 1039625.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish625.7 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
0AMH22 1040
423.4TFC
2.5MGOMAG COAT
79.6TF
625.7AMH22 1039
376.4TFC
625.7SAV
80.6TFC
2.5SAV
518.6TFA
571.9TFC
128.5TFC
0MWM
33.7TFC
229.6TFA
625.7MGOCONNECTION AT MH, 3 O'CLOCK
182.1TFC
0MWL
475TFC
323.2TFC
275.9TF

Properties (7)

additional_info
630138120220201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2020-12-02T22:25:36-08:00
documentation
PROPIPE
is_lateral_inspection
false