Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 2, 2020, 09:12 PM
  • A 1169_A 0430_12022020_132012.mp4

Date
12/02/2020
W/O
854904
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00973
PipeID
P04556
Time
1:12 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8227
Sewer Name
JOINT OUTFALL A - UNIT 9
City
SOUTH GATE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
WO_854904_TV02260_OCT2020
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
42 in.
Width
27 in.
Upstream MH
A 0430
Downstream MH
A 1169
Dir. of Survey
Upstream
Length Surveyed
14.1 ft.
Total Length
14.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3122
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole A 0430 to A 1169
MH: A 0430MH: A 1169upstream0 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - A 1169 (ZOOMED IN)1 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - MISSING TILES1 ft. OBM - Obstacles Pipe Material, 15 %of cross sectional area, from 05 to 07 o'clock7 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES12.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start14.1 ft. MWM - Water Mark, 20 %of cross sectional area14.1 ft. MWL - Water Level, 10 %of cross sectional area14.1 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK14.1 ft. AMH - Downstream Manhole, Survey Begins - A 0430

Observation photos (3)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES

    7.1 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MISSING TILES

  • Obstacles Pipe Material, 15 %of cross sectional area, from 05 to 07 o'clock

    13.1 ft. - Obstacles Pipe Material, 15 %of cross sectional area, from 05 to 07 o'clock

Observations (10)

DistanceCodeObservation
13.1SZMISSING TILES
14.1DAGS
0MWM
0MWL
14.1AMHA 1169 (ZOOMED IN)
7.1SZMISSING TILES
0MGOCONNECTION AT MH, 9 O'CLOCK
13.1OBM
0AMHA 0430
2DAGS

Properties (6)

custom_field_three
MISSING TILES
custom_field_two
3
customer
1
datetime
2020-12-02T13:12:03-08:00
documentation
PRO PIPE
is_lateral_inspection
false