Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 12, 2017, 12:11 PM
  • Section#1_29 0065_29 0064__10122017__G6850.mp4

Date
10/12/2017
W/O
0667689
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00020
PipeID
P23846
Time
5:11 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6850
Sewer Name
29 EASTSIDE INTERCEPTOR TRUNK
City
SIGNAL HILL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
20171012MDM_EASTSIDE_INTERCEPTOR_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0065
Downstream MH
29 0064
Dir. of Survey
Downstream
Length Surveyed
351.9 ft.
Total Length
351.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2I00
O&M Rating
104
Overall Index
2
Overall Quick
Overall Rating
104
Pipe schematic from manhole 29 0065 to 29 0064
MH: 29 0065MH: 29 0064downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:15AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN 3:00 ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.8 ft. MGO - General Observation - 8" VCP34.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN43.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN-80% GREASE53.2 ft. MGO - General Observation - 8" VCP79.5 ft. MWL - Water Level, 5 %of cross sectional area79.5 ft. MWM - Water Mark, 10 %of cross sectional area79.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish132.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN135 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN-50% GREASE185.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start235.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN237.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN332.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN335.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN-90% GREASE351.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish351.9 ft. AMH - Downstream Manhole, Survey Ends - 5:55AM

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 8" VCP

    8.8 ft. - General Observation - 8" VCP

  • General Observation - 8" VCP

    53.2 ft. - General Observation - 8" VCP

  • Water Mark, 10 %of cross sectional area

    79.5 ft. - Water Mark, 10 %of cross sectional area

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    185.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
332.6TFOPEN
0AMH5:15AM
0MWL
0MWM
43.1TFDOPEN-80% GREASE
235.3TFOPEN
0MGOMH CONN 3:00 ACTIVE
185.7DAGS
79.5MWL
351.6DAGS
132.1TFOPEN
53.2MGO8" VCP
79.5MWM
8.8MGO8" VCP
351.9AMH5:55AM
135TFDOPEN-50% GREASE
79.5DAGS
237.8TFOPEN
2DAGS
335.6TFDOPEN-90% GREASE
34.6TFOPEN

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2017-10-12T05:11:11-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection