Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2020, 08:45 AM
  • 22 1039_22 1038 _12032020_010007.mp4

Date
12/03/2020
W/O
854886
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00811
PipeID
P17408
Time
12:45 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8322
Sewer Name
IRWINDALE TRUNK, SECTION 1
City
IRWINDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
WO_854886_TV22137_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
22 1039
Downstream MH
22 1038
Dir. of Survey
Downstream
Length Surveyed
425 ft.
Total Length
425 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
255
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
255
Pipe schematic from manhole 22 1039 to 22 1038
MH: 22 1039MH: 22 1038downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 10390 ft. MWM - Water Mark, 20 %of cross sectional area0.1 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK2.1 ft. MGO - General Observation - MAG COAT2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start97.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"199.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"292.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"386.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"425 ft. AMH - Downstream Manhole, Survey Ends - 22 1038425 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
97.6TFC
2.1MGOMAG COAT
0MWL
425AMH22 1038
0AMH22 1039
386.2TF
292.8TFC
0MWM
2.2SAV
425SAV
199.2TFC
0.1MGOCONNECTION AT MH, 3 O'CLOCK

Properties (7)

additional_info
630138120220202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2020-12-03T00:45:40-08:00
documentation
PROPIPE
is_lateral_inspection
false