Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 19, 2020, 06:52 AM
  • C 0346_C 0345 _11182020_233616.mp4

Date
11/18/2020
W/O
855311
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00138
PipeID
P09809
Time
10:52 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8304
Sewer Name
JOINT OUTFALL C - UNIT 7B
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_855311_TV03115_OCT2020
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
15 in.
Upstream MH
C 0345
Downstream MH
C 0346
Dir. of Survey
Upstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole C 0345 to C 0346
MH: C 0345MH: C 0346upstream0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES0 ft. MSA - Survey Abandoned - VIEW OF U/S SIPHON FROM D/S MH2.1 ft. AMH - Downstream Manhole, Survey Begins - C 03452.1 ft. MGO - General Observation - CONNECTION @ D/S MH - 9 O'CLOCK2.1 ft. MWL - Water Level, 25 %of cross sectional area2.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2.1 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF U/S SIPHON FROM D/S MH

    2.1 ft. - Survey Abandoned - VIEW OF U/S SIPHON FROM D/S MH

Observations (7)

DistanceCodeObservation
2.1SAV
0AMHC 0345
2.1MSAVIEW OF U/S SIPHON FROM D/S MH
0MGOCONNECTION @ D/S MH - 9 O'CLOCK
0MWL
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWM

Properties (7)

additional_info
630075111820202
custom_field_three
AGGREGATE PROJECTING/ REINFOREMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-11-18T22:52:07-08:00
documentation
PROPIPE
is_lateral_inspection
false