Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 19, 2020, 07:36 AM
  • C 0345_C 0344 _11192020_010453.mp4

Date
11/18/2020
W/O
855311
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00138
PipeID
P09808
Time
11:36 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8304
Sewer Name
JOINT OUTFALL C - UNIT 7B
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_855311_TV03115_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
15 in.
Upstream MH
C 0345
Downstream MH
C 0344
Dir. of Survey
Downstream
Length Surveyed
456.4 ft.
Total Length
456.4 ft.
Structural Index
4
Structural Quick
5Q3Q
Structural Rating
728
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
728
Pipe schematic from manhole C 0345 to C 0344
MH: C 0345MH: C 0344downstream0 ft. MGO - General Observation - STOP LOG PRESENT APPROX. @ BEGINNING OF SECTION0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - C 03450 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start456.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish456.4 ft. AMH - Downstream Manhole, Survey Ends - C 0344456.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MGOSTOP LOG PRESENT APPROX. @ BEGINNING OF SECTION
0MGOCONNECTION AT MH 3 O'CLOCK
0AMHC 0345
0MWM
2.1SRV
0MWL
456.4AMHC 0344
2.1SAP
0MGOCONNECTION AT MH 9 O'CLOCK
456.4SRV
456.3SAP

Properties (7)

additional_info
630075111820202
custom_field_three
AGGREGATE PROJECTING/ REINFOREMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-11-18T23:36:27-08:00
documentation
propipe
is_lateral_inspection
false