Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2020, 07:32 AM
  • 15 0400_15 0399_11122020_234940.mp4

Date
11/12/2020
W/O
855306
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00597
PipeID
P12323
Time
11:32 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8193
Sewer Name
ARROYO DRIVE TRUNK
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_855306_TV15214_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 0400
Downstream MH
15 0399
Dir. of Survey
Downstream
Length Surveyed
258.1 ft.
Total Length
258.1 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
18
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
23
Pipe schematic from manhole 15 0400 to 15 0399
MH: 15 0400MH: 15 0399downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 OCLOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 04000 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES7.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"47.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"56.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"82 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES89.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start106.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"114.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"129.5 ft. RFJ - Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES156.7 ft. B - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES160 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.6 ft. RPZ - Repair Other, within 8 inches of joint: YES - LINK PIPE169.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"216.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"249 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"250.6 ft. B - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES255.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish255.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish255.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish258.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0399258.1 ft. MGO - General Observation - CONNECTION AT MH 3 AND 9 OCLOCK

Observation photos (9)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    82 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    89.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES

    129.5 ft. - Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

    156.7 ft. - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Repair Other, within 8 inches of joint: YES - LINK PIPE

    164.6 ft. - Repair Other, within 8 inches of joint: YES - LINK PIPE

  • Broken, from 08 to 10 o'clock, within 8 inches of joint: YES

    250.6 ft. - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
7.3TFC
4CM
255.4DAGS
0MGOACTIVE CONNECTION AT MH 3 OCLOCK
82CL
106.8TFC
206.5TFC
164.6RPZLINK PIPE
160TFC
249TFC
216.1TFC
0MWL
169.1TFC
56.8TFC
0AMH15 0400
129.5RFJ
156.7B
258.1AMH15 0399
47.8TFC
255.4CM
2DAE
114.1TFC
258.1MGOCONNECTION AT MH 3 AND 9 OCLOCK
2DAGS
250.6B
89.4CM
255.4DAE
0MWM

Properties (7)

additional_info
630069111220202
custom_field_three
BROKEN PIPE/MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2020-11-12T23:32:52-08:00
documentation
PRO PIPE
is_lateral_inspection
false