Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2020, 07:39 AM
  • 22 0856_22 0855 _12032020_235234.mp4

Date
12/03/2020
W/O
854654
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00803
PipeID
P17222
Time
11:39 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8324
Sewer Name
DALTON TRUNK, SECTION 3
City
AZUSA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_854654_TV22158_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
22 0856
Downstream MH
22 0855
Dir. of Survey
Downstream
Length Surveyed
388.2 ft.
Total Length
388.2 ft.
Structural Index
4
Structural Quick
5233
Structural Rating
19
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
19
Pipe schematic from manhole 22 0856 to 22 0855
MH: 22 0856MH: 22 0855downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 08560 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area3.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.5 ft. MGO - General Observation - MAG COAT21.9 ft. SAP - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES21.9 ft. SRV - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES24.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"28.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish28.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start28.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start124.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"281.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"325.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"388.2 ft. AMH - Downstream Manhole, Survey Ends - 22 0855388.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish388.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES

    21.9 ft. - Surface Aggregate Projecting, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES

    21.9 ft. - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    28.5 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    28.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
21.9SAP
168.5TF
28.5SAV
0AMH22 0856
3.5SAV
21.9SRV
28.5SRV
325.7TFC
0MWL
24.4TFC
388.2AMH22 0855
388.2SAP
3.5MGOMAG COAT
124.5TFC
281.3TFC
388.2SRV
28.5SAP
0MWM

Properties (7)

additional_info
830075120320201
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-12-03T23:39:31-08:00
documentation
PROPIPE
is_lateral_inspection
false