Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 16, 2018, 12:47 PM
  • Section#3_08 0285_08 0284__8162018__I0051.mp4

Date
08/16/2018
W/O
0722683
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00012
PipeID
P00329
Time
5:47 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0051
Sewer Name
08 JAMES STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20180815MDM_JAMES_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0285
Downstream MH
08 0284
Dir. of Survey
Downstream
Length Surveyed
241.6 ft.
Total Length
241.6 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
2
O&M Quick
2900
O&M Rating
18
Overall Index
2
Overall Quick
Overall Rating
25
Pipe schematic from manhole 08 0285 to 08 0284
MH: 08 0285MH: 08 0284downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:05AM0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area4.5 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SLIGHT16.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start29.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB57.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE61.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish128.5 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H128.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN200.3 ft. MGO - General Observation - 12" VCP229.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB241.6 ft. AMH - Downstream Manhole, Survey Ends - 5:25AM

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    16.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 12" VCP

    200.3 ft. - General Observation - 12" VCP

Observations (13)

DistanceCodeObservation
0AMH5:05AM
241.6AMH5:25AM
16.2DAGS
0MWL
200.3MGO12" VCP
57.8FLHAIRLINE
61.2DAGS
128.5FCH
4.5FCSLIGHT
229.4TFCSTUB
0MWM
29.2TFCSTUB
128.5TFOPEN

Properties (6)

custom_field_three
SLIGHT FRACTURE
custom_field_two
3
customer
LACSD
datetime
2018-08-16T05:47:47-07:00
documentation
MARTIN,REVELES,OLIVER 111,YOUNG
is_lateral_inspection
false