Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2017, 05:30 PM
  • 30 0253_30 0160_3102017_102507.mp4

  • 30 0253_30 0160_3102017_102624.mp4

Date
03/10/2017
W/O
0619108
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00876
PipeID
P17954
Time
9:30 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7357
Sewer Name
30 PLAZA TRUNK
City
PALOS VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
09
Purpose
Routine Assessment
Project
20170310DF_PLAZA_TRUNK
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
30 0253
Downstream MH
30 0160
Dir. of Survey
Downstream
Length Surveyed
231.8 ft.
Total Length
231.8 ft.
Structural Index
3
Structural Quick
5142
Structural Rating
43
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
45
Pipe schematic from manhole 30 0253 to 30 0160
MH: 30 0253MH: 30 0160downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 10:24 AM0.1 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start42.8 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES42.8 ft. BSV - Broken Soil Visible, from 08 to 11 o'clock, within 8 inches of joint: YES43.5 ft. FM - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES54.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES55.4 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES58.4 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES95.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES99.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"113.8 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES165.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES172.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES219.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES221.8 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR - 10 %224.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 10 %224.4 ft. MGP - General Photograph - 10 % ROOTS227.4 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES230.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish230.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish230.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish231.8 ft. AMH - Downstream Manhole, Survey Ends - 11:03 AM

Observation photos (16)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

    42.8 ft. - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Broken Soil Visible, from 08 to 11 o'clock, within 8 inches of joint: YES

    42.8 ft. - Broken Soil Visible, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    43.5 ft. - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    54.1 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    55.4 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    58.4 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    95.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

    113.8 ft. - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    165.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    172.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    219.2 ft. - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR - 10 %

    221.8 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR - 10 %

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 10 %

    224.4 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 10 %

  • General Photograph - 10 % ROOTS

    224.4 ft. - General Photograph - 10 % ROOTS

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    227.4 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
230.8SAV
2CL
224.4RFJ10 %
42.8FC
0.1MWM
54.1CL
2SSS
58.4CL
99.5TFC
224.4MGP10 % ROOTS
165.7CL
227.4CL
230.8CM
172.4FL
221.8RFJ10 %
230.8SSS
2SAV
55.4CL
43.5FM
231.8AMH11:03 AM
0MWL
95.4FM
2CM
219.2FL
42.8BSV
113.8FC
0AMH10:24 AM

Properties (6)

custom_field_three
FRACTURES/BROKEN PIPE
custom_field_two
2
customer
LACSD
datetime
2017-03-10T09:30:39-08:00
documentation
FRANKLIN, BRAR
is_lateral_inspection
false