Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 27, 2017, 11:42 AM
  • J 0177_J 0176 _01272017_040312.mp4

Date
01/27/2017
W/O
619081
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00055
PipeID
P11416
Time
3:42 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4095
Sewer Name
J JOINT OUTFALL J - UNIT 1C
City
SAN PEDRO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47A
Purpose
Routine Assessment
Project
WO_619081_TV05161_FEB2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
J 0177
Downstream MH
J 0176
Dir. of Survey
Downstream
Length Surveyed
517.5 ft.
Total Length
517.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole J 0177 to J 0176
MH: J 0177MH: J 0176downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 01770 ft. MWL - Water Level, 20 %of cross sectional area2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - MAGNEZIUM H.O COATING start224.8 ft. MGP - General Photograph513.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish513.1 ft. MGO - General Observation - MAGNEZIUM H.O COATING finish513.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish517.5 ft. MGO - General Observation - CCTV FOOTAGE DIFFERENT FROM SPREAD SHEET517.5 ft. AMH - Downstream Manhole, Survey Ends - J 0176

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    224.8 ft. - General Photograph

Observations (12)

DistanceCodeObservation
2.3DAGS
0MWM
2.3SAV
517.5MGOCCTV FOOTAGE DIFFERENT FROM SPREAD SHEET
0AMHJ 0177
517.5AMHJ 0176
513.1SAV
0MWL
2.3MGOMAGNEZIUM H.O COATING start
513.1MGOMAGNEZIUM H.O COATING finish
513.1DAGS
224.8MGP

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2017-01-27T03:42:10-08:00
documentation
PRO PIPE
is_lateral_inspection
false