Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 19, 2020, 10:17 AM
  • 22 1010_22 1008_11192020_023519.mp4

Date
11/19/2020
W/O
854940
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00819
PipeID
P17379
Time
2:17 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8252
Sewer Name
LORAINE TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_854940_TV22109_OCT2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 1008
Downstream MH
22 1010
Dir. of Survey
Upstream
Length Surveyed
451.2 ft.
Total Length
451.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 22 1008 to 22 1010
MH: 22 1008MH: 22 1010upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 10101.8 ft. MGO - General Observation - ROACHES IN MH1.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish16 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"65 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"88.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"141.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"218.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"317.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"345.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"398.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"438 ft. MGO - General Observation - MAG COATING THROUGHOUT449.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start449.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start451.2 ft. MWM - Water Mark, 40 %of cross sectional area451.2 ft. MWL - Water Level, 10 %of cross sectional area451.2 ft. AMH - Downstream Manhole, Survey Begins - 22 1008

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    13.2 ft. - General Observation - MAG COATING THROUGHOUT

  • General Observation - ROACHES IN MH

    449.4 ft. - General Observation - ROACHES IN MH

Observations (18)

DistanceCodeObservation
53TFC
2DAGS
449.4MGOROACHES IN MH
2SAP
386.2TFC
0MWM
0MWL
105.6TFC
435.2TFC
309.7TFC
133.8TFC
13.2MGOMAG COATING THROUGHOUT
449.4SAP
451.2AMH22 1010
0AMH22 1008
363TFC
449.4DAGS
232.5TFC

Properties (7)

additional_info
630069111820201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2020-11-19T02:17:23-08:00
documentation
PRO PIPE
is_lateral_inspection
false