Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 19, 2020, 05:59 AM
  • 22 1007_22 1006_11182020_221636.mp4

Date
11/18/2020
W/O
854940
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00819
PipeID
P17377
Time
9:59 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8252
Sewer Name
LORAINE TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_854940_TV22109_OCT2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 1007
Downstream MH
22 1006
Dir. of Survey
Downstream
Length Surveyed
342 ft.
Total Length
342 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 22 1007 to 22 1006
MH: 22 1007MH: 22 1006downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - ROACHES IN MH0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 10070 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start3.6 ft. MGO - General Observation - MAG COATING THROUGHOUT74.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"77.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"117.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"223.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"256.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"285.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"313.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"321.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"340.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish340.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish340.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish342 ft. MGO - General Observation - RECORDING CAMERA RETR. FOR COUNTER PRECISION342 ft. AMH - Downstream Manhole, Survey Ends - 22 1006

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    3.6 ft. - General Observation - MAG COATING THROUGHOUT

  • General Observation - RECORDING CAMERA RETR. FOR COUNTER PRECISION

    342 ft. - General Observation - RECORDING CAMERA RETR. FOR COUNTER PRECISION

Observations (24)

DistanceCodeObservation
0MWL
2DAGS
321.4TFA
340.6DAGS
2SAP
340.6SSS
0MGOROACHES IN MH
0MWM
223.6TFA
74.2TFC
175.3TFA
3.6MGOMAG COATING THROUGHOUT
256.5TFA
342MGORECORDING CAMERA RETR. FOR COUNTER PRECISION
285.9TFA
2SSS
0AMH22 1007
342AMH22 1006
117.9TFA
0MGOCONNECTION AT MH 3 OCLOCK
77.2TFA
340.6SAP
195.3TFA
313.8TFC

Properties (7)

additional_info
630069111820201
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2020-11-18T21:59:58-08:00
documentation
PRO PIPE
is_lateral_inspection
false