Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 30, 2020, 09:55 AM
  • 32 0109_32 0261_10302020_030730.mp4

Date
10/30/2020
W/O
849890
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P23687
Time
2:55 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8177
Sewer Name
DISTRICT #32 MAIN TRUNK
City
VALENCIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_849890_TV32048_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
32 0109
Downstream MH
32 0261
Dir. of Survey
Downstream
Length Surveyed
168.6 ft.
Total Length
168.6 ft.
Structural Index
3
Structural Quick
523E
Structural Rating
140
O&M Index
2
O&M Quick
2F00
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
206
Pipe schematic from manhole 32 0109 to 32 0261
MH: 32 0109MH: 32 0261downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01090 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start4.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start80.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start148.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES157.8 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES166.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish166.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish166.3 ft. MGO - General Observation - COCKROACHES IN MH166.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish168.6 ft. AMH - Downstream Manhole, Survey Ends - 32 0261

Observation photos (7)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.9 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    80.7 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

    148.5 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

    157.8 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    166.3 ft. - General Observation - COCKROACHES IN MH

Observations (14)

DistanceCodeObservation
0AMH32 0109
0MWM
0MWL
2DAGS
148.5SRV
80.7SSS
157.8SRV
166.3SSS
0MGOCOCKROACHES IN MH
166.3SAP
4.9SAP
166.3MGOCOCKROACHES IN MH
166.3DAGS
168.6AMH32 0261

Properties (7)

additional_info
6301029200138P1
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2020-10-30T02:55:47-07:00
documentation
PRO PIPE
is_lateral_inspection
false