Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 27, 2020, 09:51 AM
  • 32 0144_32 0143 _10272020_030740.mp4

Date
10/27/2020
W/O
849890
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19892
Time
2:51 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8173
Sewer Name
DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_849890_TV32048_SEP2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0144
Downstream MH
32 0143
Dir. of Survey
Downstream
Length Surveyed
520.8 ft.
Total Length
520.8 ft.
Structural Index
3
Structural Quick
3T00
Structural Rating
309
O&M Index
2
O&M Quick
412T
O&M Rating
210
Overall Index
3
Overall Quick
Overall Rating
519
Pipe schematic from manhole 32 0144 to 32 0143
MH: 32 0144MH: 32 0143downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01440 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start518 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish518 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish520.8 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK520.8 ft. AMH - Downstream Manhole, Survey Ends - 32 0143520.8 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    520.8 ft. - General Observation - COCKROACHES IN MH

Observations (10)

DistanceCodeObservation
0MWL
518DAGS
2SAP
520.8MGOCONNECTION AT MH, 9 O'CLOCK
0AMH32 0144
0MWM
520.8AMH32 0143
520.8MGOCOCKROACHES IN MH
2DAGS
518SAP

Properties (6)

custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2020-10-27T02:51:24-07:00
documentation
PRO PIPE
is_lateral_inspection
false