Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 30, 2020, 06:34 AM
  • 32 0132_32 0131A_10292020_234536.mp4

Date
10/29/2020
W/O
849890
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19879
Time
11:34 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8177
Sewer Name
DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_849890_TV32048_SEP2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0132
Downstream MH
32 0131A
Dir. of Survey
Downstream
Length Surveyed
275.3 ft.
Total Length
275.3 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
270
O&M Index
2
O&M Quick
412J
O&M Rating
112
Overall Index
2
Overall Quick
Overall Rating
382
Pipe schematic from manhole 32 0132 to 32 0131A
MH: 32 0132MH: 32 0131Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01320 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start273 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish273.1 ft. MGO - General Observation - COCKROACHES IN MH273.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish273.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish275.3 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK275.3 ft. AMH - Downstream Manhole, Survey Ends - 32 0131A

Observation photos (5)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    273.1 ft. - General Observation - COCKROACHES IN MH

Observations (13)

DistanceCodeObservation
0AMH32 0132
0MWL
273.1MGOCOCKROACHES IN MH
273.1DAGS
273.1SAP
275.3MGOCONNECTION AT MH, 3 O'CLOCK
275.3AMH32 0131A
0MWM
273SSS
0MGOCOCKROACHES IN MH
2.2SSS
2SAP
2DAGS

Properties (7)

additional_info
6301029200138P1
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2020-10-29T23:34:02-07:00
documentation
PRO PIPE
is_lateral_inspection
false