Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 25, 2020, 07:35 AM
  • 18 0794_18 0793_11242020_234251.mp4

Date
11/24/2020
W/O
855318
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14652
Time
11:35 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8317
Sewer Name
SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_855318_TV18182_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0794
Downstream MH
18 0793
Dir. of Survey
Downstream
Length Surveyed
54.7 ft.
Total Length
54.7 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 18 0794 to 18 0793
MH: 18 0794MH: 18 0793downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 07940 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED2.4 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Start54.7 ft. AMH - Downstream Manhole, Survey Ends - 18 079354.7 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0AMH18 0794
54.7AMH18 0793
54.7FM
0MWM
2.4FM
0MGOCONNECTION AT MH 3 O'CLOCK CAPPED
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK CAPPED

Properties (7)

additional_info
630075112420202
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2020-11-24T23:35:27-08:00
documentation
PROPIPE
is_lateral_inspection
false