- Date
- 11/25/2020
- W/O
- 855021
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00165
- PipeID
- P10539
- Time
- 4:11 AM
- Certificate
- U-115-06022794
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K8223
- Sewer Name
- JOINT OUTFALL H - UNIT 1F
- City
- HUNTINGTON PARK
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 08
- Purpose
- Routine Assessment
- Project
- RFIR_WO_855021_TV01220_OCT2020
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Square
- Height
- 36 in.
- Width
- 36 in.
- Upstream MH
- H 0086
- Downstream MH
- H 0087
- Dir. of Survey
- Upstream
- Length Surveyed
- 737.7 ft.
- Total Length
- 737.7 ft.
- Structural Index
- 3
- Structural Quick
- 5\3\
- Structural Rating
- 1470
- O&M Index
- 2
- O&M Quick
- 312\
- O&M Rating
- 297
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 1767
Pipe schematic from manhole H 0086 to H 0087 Observation photos (6)

2 ft. - General Observation - 65% MAG COAT

2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

736.7 ft. - Obstacles Pipe Material, 15 %of cross sectional area, from 05 to 06 o'clock

737.7 ft. - Survey Abandoned - COMPLETED REVERSAL