Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 25, 2020, 09:25 AM
  • H 0097_H 0096_11252020_013033.mp4

Date
11/25/2020
W/O
855021
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00165
PipeID
P10549
Time
1:25 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8223
Sewer Name
JOINT OUTFALL H - UNIT 1F
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_855021_TV01220_OCT2020
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
H 0096
Downstream MH
H 0097
Dir. of Survey
Upstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole H 0096 to H 0097
MH: H 0096MH: H 0097upstream0 ft. MSA - Survey Abandoned - VIEW OF SIPHON UPLEG0.1 ft. MGO - General Observation - 55% MAG COAT0.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES0.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. MWM - Water Mark, 100 %of cross sectional area2.1 ft. AMH - Downstream Manhole, Survey Begins - H 00962.1 ft. MWL - Water Level, 100 %of cross sectional area

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF SIPHON UPLEG

    2.1 ft. - Survey Abandoned - VIEW OF SIPHON UPLEG

Observations (7)

DistanceCodeObservation
0MWM
2MGO55% MAG COAT
0AMHH 0096
2SSS
2SAV
0MWL
2.1MSAVIEW OF SIPHON UPLEG

Properties (6)

custom_field_three
REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-11-25T01:25:55-08:00
documentation
PRO PIPE
is_lateral_inspection
false