Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 25, 2020, 09:50 AM
  • H 0094_H 0093_11252020_020438.mp4

Date
11/25/2020
W/O
855021
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00165
PipeID
P10546
Time
1:50 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8223
Sewer Name
JOINT OUTFALL H - UNIT 1F
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_855021_TV01220_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
H 0094
Downstream MH
H 0093
Dir. of Survey
Downstream
Length Surveyed
302.9 ft.
Total Length
302.9 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
300
O&M Index
2
O&M Quick
2K00
O&M Rating
120
Overall Index
2
Overall Quick
Overall Rating
420
Pipe schematic from manhole H 0094 to H 0093
MH: H 0094MH: H 0093downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 00940 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 65% MAG COAT300 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish300 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish302 ft. MGO - General Observation - AIRLINE @ MH302.9 ft. AMH - Downstream Manhole, Survey Ends - H 0093

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 65% MAG COAT

    2 ft. - General Observation - 65% MAG COAT

Observations (12)

DistanceCodeObservation
0MWM
300DAGS
300SAP
302.9AMHH 0093
302MGOAIRLINE @ MH
2SAP
2SSS
0AMHH 0094
0MWL
2DAGS
301.5SSS
2MGO65% MAG COAT

Properties (6)

custom_field_three
AGGREGATE VISIBLE/PROJECTING
custom_field_two
2
customer
1
datetime
2020-11-25T01:50:29-08:00
documentation
PRO PIPE
is_lateral_inspection
false