Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 25, 2020, 10:46 AM
  • H 0088_H 0087_11252020_031101.mp4

Date
11/25/2020
W/O
855021
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00165
PipeID
P10540
Time
2:46 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8223
Sewer Name
JOINT OUTFALL H - UNIT 1F
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_855021_TV01220_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0088
Downstream MH
H 0087
Dir. of Survey
Downstream
Length Surveyed
647.9 ft.
Total Length
647.9 ft.
Structural Index
4
Structural Quick
5r3Y
Structural Rating
1925
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
1925
Pipe schematic from manhole H 0088 to H 0087
MH: H 0088MH: H 0087downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 00880 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 55% MAG COAT2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start644.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish644.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish644.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish645 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish647.9 ft. AMH - Downstream Manhole, Survey Ends - H 0087

Observation photos (4)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 55% MAG COAT

    2 ft. - General Observation - 55% MAG COAT

Observations (13)

DistanceCodeObservation
0MWM
2SRV
647.9AMHH 0087
644.2SAP
2SAP
0AMHH 0088
0MWL
644.2SSS
2SSS
2MGO55% MAG COAT
644.2SRV
2SRC
645SRC

Properties (6)

custom_field_three
REINFORCEMENT VISIBLE/REINFORCEMENT CORRODED
custom_field_two
2
customer
1
datetime
2020-11-25T02:46:47-08:00
documentation
PRO PIPE
is_lateral_inspection
false