Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2020, 08:58 AM
  • 29 0029_C 0663_11042020_010730.mp4

Date
11/04/2020
W/O
854871
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00266
PipeID
P23930
Time
12:58 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8145
Sewer Name
JOINT OUTFALL C - UNIT 3F
City
SIGNAL HILL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_854871_TV29113_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
29 0029
Downstream MH
C 0663
Dir. of Survey
Downstream
Length Surveyed
329 ft.
Total Length
329 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 29 0029 to C 0663
MH: 29 0029MH: C 0663downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 00290 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area3.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start96.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"144.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"196.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"243.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"296.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"329 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329 ft. AMH - Downstream Manhole, Survey Ends - C 0663

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    196.7 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    243.9 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    296.8 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (12)

DistanceCodeObservation
329CM
3.7CM
144.6TF
0MWL
0AMH29 0029
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
243.9TB
196.7TB
296.8TB
96.5TF
329AMHC 0663

Properties (8)

additional_info
6301103200075P2
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-11-04T00:58:10-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
37482