Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 24, 2020, 06:37 AM
  • 05 0899_05 0898_11232020_225617.mp4

Date
11/23/2020
W/O
855307
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00512
PipeID
P06129
Time
10:37 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8313
Sewer Name
RAYMOND AVENUE TRUNK
City
hawthorne
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_855307_TV05204_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0899
Downstream MH
05 0898
Dir. of Survey
Downstream
Length Surveyed
312.5 ft.
Total Length
312.5 ft.
Structural Index
4
Structural Quick
4231
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
11
Pipe schematic from manhole 05 0899 to 05 0898
MH: 05 0899MH: 05 0898downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 08990 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area3.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"65.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"75 ft. FM - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES79.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"113.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"122.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"122.2 ft. FM - Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES, Start127.6 ft. FM - Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES, Finish142.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.6 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"202.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"218.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"233.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"255 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"285.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"286.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"298.4 ft. TS - Tap Saddle, at 01 o'clock, -, within 8 inches of joint: YES, 6"312.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish312.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK312.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0898312.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    75 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    79.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    122.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES, Start

    122.2 ft. - Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    168.6 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    218.9 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    298.4 ft. - Tap Saddle, at 01 o'clock, -, within 8 inches of joint: YES, 6"

Observations (28)

DistanceCodeObservation
122.2TB
0AMH05 0899
312.3CM
65.8TFC
202.7TFC
0MGOCONNECTION AT MH 3 O'CLOCK
122.2FM
285.7TF
0MWM
255TFC
312.5MGOCONNECTION AT MH 3 O'CLOCK
3.2CM
168.6TB
79.2TF
79.2TB
113.9TFC
15.7TF
218.9TB
312.5AMH05 0898
233.2TF
286.3TFC
142.1TF
0MWL
75FM
127.6FM
298.4TS
159.8TFC
312.5MGOCONNECTION AT MH 9 O'CLOCK

Properties (7)

additional_info
630075112320202
custom_field_three
MULTIPLEM CRACKS/ FRACTURES
custom_field_two
2
customer
1
datetime
2020-11-23T22:37:25-08:00
documentation
PROPIPE
is_lateral_inspection
false