Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 24, 2020, 05:22 AM
  • 05 1045_05 0115_11232020_214439.mp4

Date
11/23/2020
W/O
855113
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00441
PipeID
P06280
Time
9:22 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8312
Sewer Name
FLOWER STREET TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_855113_TV05195_OCT2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
10 in.
Upstream MH
05 1045
Downstream MH
05 0115
Dir. of Survey
Downstream
Length Surveyed
332.5 ft.
Total Length
332.5 ft.
Structural Index
3
Structural Quick
4131
Structural Rating
9
O&M Index
2
O&M Quick
3111
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 05 1045 to 05 0115
MH: 05 1045MH: 05 0115downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 10450 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK capped0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"13.3 ft. MGO - General Observation - joint broken14.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"14.9 ft. RFL - Roots Fine Lateral, at 10 o'clock43.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish43.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start54.2 ft. TSI - Tap Saddle Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"84.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"139.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"141.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"160.6 ft. MWLS - Water Level, Sag in pipe, 25 %of cross sectional area185.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"207.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"255.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"258.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"294.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"297.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"332.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish332.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK332.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0115

Observation photos (6)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    11 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • General Observation - joint broken

    13.3 ft. - General Observation - joint broken

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    43.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

    54.2 ft. - Tap Saddle Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

  • Water Level, Sag in pipe, 25 %of cross sectional area

    160.6 ft. - Water Level, Sag in pipe, 25 %of cross sectional area

Observations (28)

DistanceCodeObservation
294.5TF
332.5FM
160.6MWLS
54.2TSI
297.6TFC
141.6TF
84.5TF
43.5CM
207.7TFC
255.7TF
0AMH05 1045
258.6TF
185.4TFA
11TB
0MGOCONNECTION AT MH 3 O'CLOCK capped
14.9TF
0MGOCONNECTION AT MH 9 O'CLOCK
14.9RFL
13.3MGOjoint broken
2.3CM
43.6FM
127.3TFC
0MWL
0MWM
210.5TF
332.5MGOCONNECTION AT MH 9 O'CLOCK
332.5AMH05 0115
139.1TFC

Properties (7)

additional_info
630075112320201
custom_field_three
multiple fracture's
custom_field_two
2
customer
1
datetime
2020-11-23T21:22:36-08:00
documentation
PROPIPE
is_lateral_inspection
false