Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2017, 08:07 AM
  • 21 0821A_21 0821_6232017_011845.mp4

Date
06/23/2017
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00772
PipeID
P15922
Time
1:07 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0572
Sewer Name
21 LA VERNE TRUNK, SECTION 2
City
LA VERN
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
05
Purpose
Routine Assessment
Project
20170623MDM_LA_VERN_TRUNK_SECTION_2
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
21 0821A
Downstream MH
21 0821
Dir. of Survey
Downstream
Length Surveyed
76.4 ft.
Total Length
76.4 ft.
Structural Index
2
Structural Quick
3824
Structural Rating
34
O&M Index
5
O&M Quick
5200
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
44
Pipe schematic from manhole 21 0821A to 21 0821
MH: 21 0821AMH: 21 0821downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 1:10AM0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - 63 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - HAIRLINE6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - HAIRLINE8.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H11.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - H11.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - H16.4 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H16.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE16.4 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - HAIRLINE18.9 ft. MGO - General Observation - CHIPPING WITH FRACTURES23.9 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - SL31.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - H33.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - H38.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H38.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H42.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - H42.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - H43.5 ft. JOM - Joint Offset Medium43.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL48.8 ft. JOM - Joint Offset Medium51.7 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 10% PIPE LOSS51.7 ft. MMC - Material Change, Cast Iron - START75.7 ft. MGP - General Photograph76.1 ft. DAGS - Deposits Attached Grease, 50 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: NO76.1 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - FINISH76.1 ft. MMC - Material Change, Vitrified clay pipe76.1 ft. MWM - Water Mark, 90 %of cross sectional area76.1 ft. MWL - Water Level, 60 %of cross sectional area76.4 ft. MSA - Survey Abandoned - 50% GREASE OR MORE

Observation photos (9)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    16.4 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • General Observation - CHIPPING WITH FRACTURES

    18.9 ft. - General Observation - CHIPPING WITH FRACTURES

  • Joint Offset Medium

    43.5 ft. - Joint Offset Medium

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 10% PIPE LOSS

    51.7 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 10% PIPE LOSS

  • Material Change, Cast Iron - START

    51.7 ft. - Material Change, Cast Iron - START

  • General Photograph

    75.7 ft. - General Photograph

  • Deposits Attached Grease, 50 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: NO

    76.1 ft. - Deposits Attached Grease, 50 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: NO

  • Survey Abandoned - 50% GREASE OR MORE

    76.4 ft. - Survey Abandoned - 50% GREASE OR MORE

Observations (34)

DistanceCodeObservation
38.9FLH
38.9FLH
6FLHAIRLINE
11.2FLH
76.1DAGS
51.7SCP10% PIPE LOSS
76.1SCPFINISH
3FLSLIGHT
51.7MMCSTART
31.9FLH
48.8JOM
42.1FLH
11.2FLH
0.5FL6
76.1MMC
42.1FLH
33.7FLH
76.1MWM
23.9FCSL
16.4FCH
0MGOConn. @ Mh, 3 O' Clock. Active
43.5JOM
3FCHAIRLINE
75.7MGP
0AMH1:10AM
76.1MWL
16.4FLHAIRLINE
8.7FCH
0MWM
76.4MSA50% GREASE OR MORE
43.5FLSL
0MWL
18.9MGOCHIPPING WITH FRACTURES
16.4FLHAIRLINE

Properties (6)

custom_field_three
LONG SLIGHT FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2017-06-23T01:07:50-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false