Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 14, 2018, 09:40 AM
  • 08 0290_08 0289_8142018_034750.mp4

Date
08/14/2018
W/O
0722683
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00012
PipeID
P00334
Time
2:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0951
Sewer Name
08 JAMES STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20180814MDM_JAMES_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0290
Downstream MH
08 0289
Dir. of Survey
Downstream
Length Surveyed
289.3 ft.
Total Length
289.3 ft.
Structural Index
2
Structural Quick
322A
Structural Rating
26
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
26
Pipe schematic from manhole 08 0290 to 08 0289
MH: 08 0290MH: 08 0289downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:45AM8 ft. MGO - General Observation - 12" VCP15 ft. MWM - Water Mark, 40 %of cross sectional area51.5 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - HAIRLINE66.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H67.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active77.9 ft. MWM - Water Mark, 30 %of cross sectional area104.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT120.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H162.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped181.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active221.4 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H241.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open246.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H248.8 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL254.7 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H268 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open276.3 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H280.6 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H280.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H284.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL289.3 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observation photos (1)

  • General Observation - 12" VCP

    8 ft. - General Observation - 12" VCP

Observations (24)

DistanceCodeObservation
254.7FCH
15MWM
162.9TFCCapped
8MGO12" VCP
77.9MWM
120.1FCH
276.3FCH
268TFOpen
181.5TFActive
241.2TBOpen
51.5FLHAIRLINE
0MWM
289.3AMH4:25AM
280.6FCH
221.4FCH
0MWL
104.9FCSLIGHT
67.6TFActive
0AMH3:45AM
246.1FCH
248.8FCSL
66.4FLH
284.5FCSL
280.6FCH

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-08-14T02:40:06-07:00
documentation
MARTIN,REVELES,OLIVER 111,YOUNG
is_lateral_inspection