Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2018, 07:23 AM
  • 08 0298_08 0297_8132018_003147.mp4

Date
08/13/2018
W/O
0722683
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00012
PipeID
P00343
Time
12:23 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0947
Sewer Name
08 JAMES STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Routine Assessment
Project
08132018VMR_JAMES_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0298
Downstream MH
08 0297
Dir. of Survey
Downstream
Length Surveyed
358.1 ft.
Total Length
358.1 ft.
Structural Index
2
Structural Quick
3622
Structural Rating
35
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
39
Pipe schematic from manhole 08 0298 to 08 0297
MH: 08 0298MH: 08 0297downstream0 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:01 AM0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Start9.7 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES18.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Capped32.1 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES58.3 ft. CC - Crack Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES72.2 ft. MWL - Water Level, 40 %of cross sectional area102 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES114 ft. CC - Crack Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES135 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"144.3 ft. CM - Crack Multiple, from 02 to 03 o'clock, within 8 inches of joint: YES150.5 ft. MWL - Water Level, 20 %of cross sectional area160.2 ft. CC - Crack Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES167.7 ft. MGP - General Photograph - Grease above water line184.1 ft. CC - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES186.5 ft. MWL - Water Level, 10 %of cross sectional area188.5 ft. CC - Crack Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES192.3 ft. CC - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES196.3 ft. CC - Crack Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES208.1 ft. CC - Crack Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES236.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES236.4 ft. MWL - Water Level, 40 %of cross sectional area241.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"250.8 ft. CC - Crack Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES258.8 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES264.2 ft. MWL - Water Level, 50 %of cross sectional area270.8 ft. CC - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES282.8 ft. CC - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES295 ft. CC - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES306.8 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES322.9 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES343.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"349.4 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES356.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Finish356.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Finish358.1 ft. AMH - Downstream Manhole, Survey Ends - 01:06 am

Observation photos (1)

  • General Photograph - Grease above water line

    167.7 ft. - General Photograph - Grease above water line

Observations (40)

DistanceCodeObservation
241.2TFC
306.8CM
9.7CM
135TFC
72.2MWL
236.4CM
0TFA
2DAGS
270.8CC
167.7MGPGrease above water line
144.3CM
356.6DAGS
358.1AMH01:06 am
102CL
0MWL
32.1CL
356.6DAGS
282.8CC
322.9CM
18.8TFCapped
343.7TFC
250.8CC
349.4CM
150.5MWL
295CC
208.1CC
196.3CC
0AMH12:01 AM
184.1CC
2DAGS
236.4MWL
264.2MWL
192.3CC
258.8CC
188.5CC
186.5MWL
114CC
58.3CC
160.2CC
0MWM

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2018-08-13T00:23:46-07:00
documentation
REVELES, OLIVER, YONG
is_lateral_inspection
false