Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2018, 08:48 PM
  • 08 0286_08 0285_8152018_141325.mp4

Date
08/15/2018
W/O
0722683
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00012
PipeID
P00330
Time
1:48 PM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7787
Sewer Name
08 JAMES STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Routine Assessment
Project
20180815SHO_JAMES_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0286
Downstream MH
08 0285
Dir. of Survey
Downstream
Length Surveyed
238.8 ft.
Total Length
238.8 ft.
Structural Index
3
Structural Quick
3900
Structural Rating
27
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
27
Pipe schematic from manhole 08 0286 to 08 0285
MH: 08 0286MH: 08 0285downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 02866 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"9 ft. FS - Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES54.3 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES71.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"72.7 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES83.8 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES96.9 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES133.5 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES139.9 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES148.3 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES171.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"177.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES238.8 ft. AMH - Downstream Manhole, Survey Ends - MH 0285

Observation photos (1)

  • Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

    9 ft. - Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
9FS
133.5CM
139.9CM
177.6CM
72.7CM
71.5TFC
54.3CM
148.3CM
0MWL
6TBA
83.8CM
96.9CM
171.1TF
0MWM
0AMHMH 0286
238.8AMHMH 0285

Properties (6)

custom_field_three
CRACKS & A SINGLE FRACTURE
custom_field_two
3
customer
LACSD
datetime
2018-08-15T13:48:34-07:00
documentation
OBREGON, BRAR, VENDRYES, PARAISO
is_lateral_inspection
false