Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2020, 05:29 AM
  • E 0028_E 0027_11172020_224233.mp4

Date
11/17/2020
W/O
855582
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00028
PipeID
P07611
Time
9:29 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8301
Sewer Name
JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
Routine Assessment
Project
WO_855582_TV01088_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
15 in.
Upstream MH
E 0028
Downstream MH
E 0027
Dir. of Survey
Downstream
Length Surveyed
528.5 ft.
Total Length
528.6 ft.
Structural Index
3
Structural Quick
3T22
Structural Rating
316
O&M Index
2
O&M Quick
2T00
O&M Rating
210
Overall Index
2
Overall Quick
Overall Rating
526
Pipe schematic from manhole E 0028 to E 0027
MH: E 0028MH: E 0027downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00282 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - 75% MAG COAT6.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start526 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish526 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish528.6 ft. AMH - Downstream Manhole, Survey Ends - E 0027 ZOOMED IN528.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
526DAGS
0MWL
2DAGS
2.3MGO75% MAG COAT
528.6AMHE 0027 ZOOMED IN
2SSS
0MWM
526SSS
0AMHE 0028
528.6SAP
6.4SAP

Properties (7)

additional_info
630075111720201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2020-11-17T21:29:55-08:00
documentation
PROPIPE
is_lateral_inspection
false