Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2020, 08:14 AM
  • 04 0067_04 0066_1252020_003453.mp4

Date
12/05/2020
W/O
0860037
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00414
PipeID
P11802
Time
12:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1651
Sewer Name
04 ROSEWOOD AVENUE EXTENSION TRUNK
City
HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
20201205MDM_ROSEWOOD_AVENUE_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
04 0067
Downstream MH
04 0066
Dir. of Survey
Downstream
Length Surveyed
317.8 ft.
Total Length
317.8 ft.
Structural Index
2
Structural Quick
322A
Structural Rating
31
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
34
Pipe schematic from manhole 04 0067 to 04 0066
MH: 04 0067MH: 04 0066downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:20AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - VERY SLIGHT FLAKING8.3 ft. MGO - General Observation - VERY SLIGHT SUFACE NICK39 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YESR - 1%77.7 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - hairline91.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped101.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped116 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H144.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped154.4 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SLIGHT168.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active-25% ROOTS190.2 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H216.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped223.5 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H229.3 ft. MGP - General Photograph - 8" VCP229.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped256.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H277.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped288 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped292.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL302.6 ft. MGP - General Photograph - 8" VCP312.9 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - H315.9 ft. MGO - General Observation - UNUSAL PIPE SURFACE316.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H317 ft. CC - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES317 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL317 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H317 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES317 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - H317.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - VERY SLIGHT FLAKING317.8 ft. AOC - Drop Connection, Survey Ends - 1:25AM

Observation photos (5)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - VERY SLIGHT FLAKING

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - VERY SLIGHT FLAKING

  • General Photograph - 8" VCP

    229.3 ft. - General Photograph - 8" VCP

  • General Photograph - 8" VCP

    302.6 ft. - General Photograph - 8" VCP

  • General Observation - UNUSAL PIPE SURFACE

    315.9 ft. - General Observation - UNUSAL PIPE SURFACE

  • Drop Connection, Survey Ends - 1:25AM

    317.8 ft. - Drop Connection, Survey Ends - 1:25AM

Observations (33)

DistanceCodeObservation
101.5TFCCapped
277.9TFCCapped
216.5TFCCapped
154.4FCSLIGHT
0MWL
317CC
256.7FCH
144.9TFCapped
312.9FCH
317FCSL
8.3MGOVERY SLIGHT SUFACE NICK
317.3SSSVERY SLIGHT FLAKING
229.3MGP8" VCP
116FCH
2SSSVERY SLIGHT FLAKING
317FLH
190.2FCH
223.5FCH
317.8AOC1:25AM
77.7FChairline
302.6MGP8" VCP
39RFJ1%
168.1TFDActive-25% ROOTS
288TFCCapped
317FC
292.4FCSL
317FCH
316.6FLH
91.3TFCCapped
0MWM
0AMH12:20AM
229.3TFCCapped
315.9MGOUNUSAL PIPE SURFACE

Properties (6)

custom_field_three
FEW SLIGHT & HAIRLINE FRACTURES
custom_field_two
4
customer
LACSD
datetime
2020-12-05T00:14:27-08:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false