Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2020, 05:35 PM
  • 1_1_1_01122020_094340.mp4

Date
12/01/2020
W/O
0860611
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00594
PipeID
P12630
Time
9:35 AM
Certificate
U-415-06024039
System Owner
1
Date Cleaned
Pre-Cleaning
Jetting
Media Label
I0363
Sewer Name
ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Maintenance Related
Project
20201201DF_ARCADIA_SIERRA_MADRE_TRUNK_SECT_3_2A
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0852
Downstream MH
15 0851
Dir. of Survey
Downstream
Length Surveyed
205.2 ft.
Total Length
205.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2G00
O&M Rating
80
Overall Index
2
Overall Quick
Overall Rating
80
Pipe schematic from manhole 15 0852 to 15 0851
MH: 15 0852MH: 15 0851downstream0 ft. AMH - Upstream Manhole, Survey Begins - 9:37 AM0.1 ft. MWL - Water Level, 15 %of cross sectional area0.1 ft. MGO - General Observation - CONN @ MH 3 0 'CLOCK/ACTIVE0.1 ft. MWM - Water Mark, 20 %of cross sectional area7.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start40.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4" - 5% ROOTS-85%ROOTS-LATERAL80.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 5% ROOTS132.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - OPEN201.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish205.2 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE205.2 ft. AMH - Downstream Manhole, Survey Ends - 10:03 AM

Observation photos (2)

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4" - 5% ROOTS-85%ROOTS-LATERAL

    40.6 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4" - 5% ROOTS-85%ROOTS-LATERAL

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 5% ROOTS

    80.3 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 5% ROOTS

Observations (11)

DistanceCodeObservation
201.9DAGS
0AMH9:37 AM
0.1MWL
80.3TF5% ROOTS
7.9DAGS
40.6TFD5% ROOTS-85%ROOTS-LATERAL
205.2MGOCONN @ MH 9 O'CLOCK/ACTIVE
132.5TFOPEN
0.1MGOCONN @ MH 3 0 'CLOCK/ACTIVE
0.1MWM
205.2AMH10:03 AM

Properties (6)

custom_field_two
4
customer
1
datetime
2020-12-01T09:35:36-08:00
documentation
FRANKLIN, RAMIREZ, IGNACIO
is_lateral_inspection
false
lining
PVCP-Folded/Reformed