Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2020, 06:02 PM
  • 1_1_1_03122020_110212.mp4

Date
12/03/2020
W/O
0855034
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00177
PipeID
P20498
Time
10:02 AM
Certificate
U-415-06024039
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0365
Sewer Name
JOINT OUTFALL H - UNIT 5A
City
WHITTIER
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
33
Purpose
Capital Improvement Program Assesment
Project
20201203DF_JOINT_OUTFALL_H_UNIT_5A
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
H 0412
Downstream MH
H 0799
Dir. of Survey
Downstream
Length Surveyed
418.9 ft.
Total Length
496.6 ft.
Structural Index
3
Structural Quick
563P
Structural Rating
445
O&M Index
2
O&M Quick
2P00
O&M Rating
166
Overall Index
2
Overall Quick
Overall Rating
611
Pipe schematic from manhole H 0412 to H 0799
MH: H 0412MH: H 0799downstream0 ft. AMH - Upstream Manhole, Survey Begins - 10:05 AM0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area1.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.3 ft. MGO - General Observation - 65% MAG COAT103.1 ft. MGP - General Photograph390.7 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start399.2 ft. MGP - General Photograph409.9 ft. MGP - General Photograph418.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish418.9 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish418.9 ft. AMH - Downstream Manhole, Survey Ends - 11:24 AM418.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish418.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (7)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    1.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 65% MAG COAT

    12.3 ft. - General Observation - 65% MAG COAT

  • General Photograph

    103.1 ft. - General Photograph

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    390.7 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    399.2 ft. - General Photograph

  • General Photograph

    409.9 ft. - General Photograph

Observations (16)

DistanceCodeObservation
418.9DAGS
418.9SRC
0AMH10:05 AM
0MWL
399.2MGP
103.1MGP
0MWM
2.4DAGS
2.7SAV
418.9AMH11:24 AM
418.9SSS
418.9SAV
12.3MGO65% MAG COAT
1.9SSS
409.9MGP
390.7SRC

Properties (6)

custom_field_three
REINFORCEMENT CORRODED/VISIBLE REINFORCEMENT
custom_field_two
2
customer
1
datetime
2020-12-03T10:02:17-08:00
documentation
FRANKLIN, IGNACIO, RAMIREZ
is_lateral_inspection
false