- Date
- 12/03/2020
- W/O
- 0855034
- Weather
- Dry
- Operator/Surveyor
- FRANKLIN
- Sewer ID
- Z00177
- PipeID
- P20498
- Time
- 10:02 AM
- Certificate
- U-415-06024039
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- I0365
- Sewer Name
- JOINT OUTFALL H - UNIT 5A
- City
- WHITTIER
- Loc. details
- Other
- Location Code
- Z
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 33
- Purpose
- Capital Improvement Program Assesment
- Project
- 20201203DF_JOINT_OUTFALL_H_UNIT_5A
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 57 in.
- Width
- 57 in.
- Upstream MH
- H 0412
- Downstream MH
- H 0799
- Dir. of Survey
- Downstream
- Length Surveyed
- 418.9 ft.
- Total Length
- 496.6 ft.
- Structural Index
- 3
- Structural Quick
- 563P
- Structural Rating
- 445
- O&M Index
- 2
- O&M Quick
- 2P00
- O&M Rating
- 166
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 611
Pipe schematic from manhole H 0412 to H 0799 Observation photos (7)

1.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

12.3 ft. - General Observation - 65% MAG COAT

103.1 ft. - General Photograph

390.7 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

399.2 ft. - General Photograph

409.9 ft. - General Photograph