- Date
- 03/11/2019
- W/O
- 0759064
- Weather
- Dry
- Operator/Surveyor
- SANTIAGO OBREGON
- Sewer ID
- Z00347
- PipeID
- P10445
- Time
- 9:02 AM
- Certificate
- U-1014-06022541
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- I0122
- Sewer Name
- G JOINT OUTFALL G - UNIT 7
- City
- COMPTON
- Loc. details
- Other
- Location Code
- Z
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 05
- Purpose
- Routine Assessment
- Project
- 20190311SHO_JOINT_OUTFALL_G_UNIT_7
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 36 in.
- Upstream MH
- G 0082
- Downstream MH
- G 0081A
- Dir. of Survey
- Downstream
- Length Surveyed
- 224.2 ft.
- Total Length
- 224.2 ft.
- Structural Index
- 3
- Structural Quick
- 3G00
- Structural Rating
- 126
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 126
Pipe schematic from manhole G 0082 to G 0081A Observation photos (2)

8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - VERY SPORADIC

85.1 ft. - General Observation - 25% MAG COAT INTACT