Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 13, 2020, 06:51 AM
  • B 0722_B 0721_10132020_002216.mp4

Date
10/12/2020
W/O
849990
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00110
PipeID
P09397
Time
11:51 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8158
Sewer Name
JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
09
Purpose
Routine Assessment
Project
WO_849990_TV15057_SEP2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
39 in.
Upstream MH
B 0722
Downstream MH
B 0721
Dir. of Survey
Downstream
Length Surveyed
385.6 ft.
Total Length
385.6 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole B 0722 to B 0721
MH: B 0722MH: B 0721downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 07220 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area8.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"66.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"177.8 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES222.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"272.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"325.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"375.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"383.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish385.6 ft. AMH - Downstream Manhole, Survey Ends - B 0721

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    177.8 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
17.1TFC
0AMHB 0722
375.4TFA
272.4TFC
0MWL
123.2TFC
385.6AMHB 0721
0MWM
222.8TFC
66.9TFC
177.8FM
173.3TF
325.6TFC
383.8SAV
8.8SAV

Properties (7)

additional_info
6301012200138P1
custom_field_three
VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2020-10-12T23:51:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false