Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 13, 2020, 09:51 AM
  • B 0715_B 0714A_10132020_030451.mp4

Date
10/13/2020
W/O
849990
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00110
PipeID
P09389
Time
2:51 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8158
Sewer Name
JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_849990_TV15057_SEP2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
39 in.
Upstream MH
B 0715
Downstream MH
B 0714A
Dir. of Survey
Downstream
Length Surveyed
245.7 ft.
Total Length
245.7 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
144
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
3
Overall Quick
Overall Rating
240
Pipe schematic from manhole B 0715 to B 0714A
MH: B 0715MH: B 0714Adownstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 07150 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"177.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"230.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"242.7 ft. MGO - General Observation - COCKROACHES IN MH242.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish242.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish245.7 ft. AMH - Downstream Manhole, Survey Ends - B 0714A245.7 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    242.7 ft. - General Observation - COCKROACHES IN MH

Observations (17)

DistanceCodeObservation
0MWM
242.7MGOCOCKROACHES IN MH
131.7TFC
0MWL
177.3TFC
31.3TFC
0AMHB 0715
245.7AMHB 0714A
242.7DAGS
2DAGS
0MGOCOCKROACHES IN MH
230.2TFC
80.8TFC
242.7SAV
0MGOCONNECTION AT MH, 9 O'CLOCK
2SAV
245.7MGOCONNECTION AT MH, 9 O'CLOCK

Properties (7)

additional_info
6301012200138P1
custom_field_three
VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2020-10-13T02:51:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false