Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 30, 2020, 10:26 AM
  • B 0714_B 0713_09302020_034717.mp4

Date
09/30/2020
W/O
849990
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00110
PipeID
P09387
Time
3:26 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8153
Sewer Name
JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_849990_TV15057_SEP2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
39 in.
Upstream MH
B 0713
Downstream MH
B 0714
Dir. of Survey
Upstream
Length Surveyed
331.5 ft.
Total Length
331.5 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
195
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
3
Overall Quick
Overall Rating
325
Pipe schematic from manhole B 0713 to B 0714
MH: B 0713MH: B 0714upstream0 ft. AMH - Upstream Manhole, Survey Ends - B 07142.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish99.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"103 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"154.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"202.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"251.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"254.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"306.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"329.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start329.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start331.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE331.5 ft. MWL - Water Level, 10 %of cross sectional area331.5 ft. MGO - General Observation - MAG COATING THROUGHOUT331.5 ft. AMH - Downstream Manhole, Survey Begins - B 0713331.5 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - MAG COATING THROUGHOUT

    0 ft. - General Observation - MAG COATING THROUGHOUT

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    329.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (21)

DistanceCodeObservation
25TFA
331.5AMHB 0714
80.4TBA
0MGOCOCKROACHES IN MANHOLE
125.8TFA
77.2TFA
329.4MGOCOCKROACHES IN MANHOLE
28TFC
179.7TFC
2DAGS
329.4SAV
228.5TFC
128.6TFC
0MWL
2SAV
329.4DAGS
176.7TFA
0MGOMAG COATING THROUGHOUT
0AMHB 0713
0MWM
231.9TFC

Properties (4)

customer
1
datetime
2020-09-30T03:26:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false