Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 30, 2020, 07:06 AM
  • B 0711_B 0710_09302020_001937.mp4

Date
09/30/2020
W/O
849990
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00110
PipeID
P09384
Time
12:06 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8153
Sewer Name
JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_849990_TV15057_SEP2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
39 in.
Upstream MH
B 0711
Downstream MH
B 0710
Dir. of Survey
Downstream
Length Surveyed
277.5 ft.
Total Length
277.5 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
2
O&M Quick
2J00
O&M Rating
110
Overall Index
3
Overall Quick
Overall Rating
275
Pipe schematic from manhole B 0711 to B 0710
MH: B 0711MH: B 0710downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - B 07112 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start30.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"94.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"143.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"198.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"271.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"275.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish275.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish277.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK277.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE277.5 ft. AMH - Downstream Manhole, Survey Ends - B 0710

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    277.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
143.1TFA
0MWM
277.5MGOCONNECTION AT MH 3 O'CLOCK
0MWL
0MGOCONNECTION AT MH 3 O'CLOCK
30.2TFC
79.3TFA
94.9TFC
275.5DAGS
2MGOMAG COATING THROUGHOUT
2SAV
277.5MGOCOCKROACHES IN MANHOLE
0MGOCOCKROACHES IN MANHOLE
271.8TBA
277.5AMHB 0710
275.5SAV
198.3TFA
2DAGS
0AMHB 0711

Properties (4)

customer
1
datetime
2020-09-30T00:06:31-07:00
documentation
PRO PIPE
is_lateral_inspection
false