Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2020, 07:37 AM
  • F 0255_F 0073 _11162020_234157.mp4

Date
11/16/2020
W/O
855024
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00035
PipeID
P10163
Time
11:37 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8212
Sewer Name
JOINT OUTFALL F - UNIT 3A
City
CERRITOS
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
WO_855024_TV02199_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
24 in.
Upstream MH
F 0255
Downstream MH
F 0073
Dir. of Survey
Downstream
Length Surveyed
41.3 ft.
Total Length
41.3 ft.
Structural Index
3
Structural Quick
5837
Structural Rating
75
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
79
Pipe schematic from manhole F 0255 to F 0073
MH: F 0255MH: F 0073downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 02550 ft. MWL - Water Level, 35 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish41 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN41.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish41.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish41.3 ft. AMH - Downstream Manhole, Survey Ends - F 0073

Observation photos (2)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
41.2SRV
39SSS
0MWM
41MGOCONN @ MH 9 O'CLOCK/OPEN
41.3AMHF 0073
0AMHF 0255
2SRV
7.9SAP
0MWL
2SSS
41.1SAP

Properties (7)

additional_info
630075111620201
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-11-16T23:37:51-08:00
documentation
PROPIPE
is_lateral_inspection
false