Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2020, 11:15 AM
  • F 0067_F 0066 _11172020_040731.mp4

Date
11/17/2020
W/O
855024
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00035
PipeID
P10152
Time
3:15 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8212
Sewer Name
JOINT OUTFALL F - UNIT 3A
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
WO_855024_TV02199_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
27 in.
Upstream MH
F 0067
Downstream MH
F 0066
Dir. of Survey
Downstream
Length Surveyed
611.4 ft.
Total Length
611.4 ft.
Structural Index
3
Structural Quick
5W3W
Structural Rating
1203
O&M Index
2
O&M Quick
2W00
O&M Rating
242
Overall Index
3
Overall Quick
Overall Rating
1445
Pipe schematic from manhole F 0067 to F 0066
MH: F 0067MH: F 0066downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 00670 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 20% MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start609 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish609 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish611.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish611.4 ft. AMH - Downstream Manhole, Survey Ends - F 0066 ZOOMED IN611.4 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    18.5 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
18.5SRV
0MWL
0AMHF 0067
609SSS
609DAGS
611.4SAP
611.4AMHF 0066 ZOOMED IN
2.1SAP
2DAGS
611.4SRV
2MGO20% MAG COAT
0MWM
2SSS

Properties (7)

additional_info
630075111620201
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-11-17T03:15:46-08:00
documentation
PROPIPE
is_lateral_inspection
false